电动机软启动器在排水系统的应用
Application of electromotor soft starter in drainage system
李载源
(广东仁化锦江电力开发总公司,广东仁化512300)
(Guangdong Renhua Electric Power Development General Corporation,Renhua 5 12300,China)
摘要:介绍了电机软启动器的基本原理和功能,分析了其在水电站排水系统中的应用情况。对电机软启动器
与传统电机控制方式进行了比较,指出了其相对传统控制方式的优点,并给出了传统控制方式改进的建议。
关键词:电机软启动器;水电站排水系统;电机控制方式
中图分类号:TM 306 文献标志码:B 文章编号:1674—1951(2008)09—0053—03
Abstract:The essential principle and function of electromotor soft starter were introduced,the application of the soft
starter in drainage system of hydroelectric power station was analyzed.The soft starter was compared with conven—
tional electromotor control mode,the advantages of soft starter over conventional eleetromotor control mode were
pointed OUt,and the improvement proposal for conventional control mode was given.
Key words:electromotor soft starter;hydroelectric power station drainage system;eleetromotor control mode
0 引言
锦江电站建成于20世纪90年代初,各电气设
备都相对落后。在最近的计算机监控系统改造中,
对集水井排水泵电动机的控制采用了近年发展起来
的电动机软启动器,取代了原有的Y一△启动方式。
水电站集水井排水是非常重要的,哪怕有一次
因故障不能抽水,都可能导致水淹水泵甚至水淹厂
房。集水井排水系统由2组IS150—125—315型水
泵配置Y2OOL一4(30 kW)型电动机和底阀、碟阀、
止回阀、DN150钢管等构成。出水管路预埋在混凝
土中固定,出水口在尾水位以下,管内长期充满有压
收稿日期:2008—08—14
力的水,底阀到尾水面有16 1i3的高差。其特点是电
动机功率大、启动电流大、水泵扬程高、排水量大。
基于集水井排水的重要性,要求水泵控制必须可靠
和稳定。
1 传统的电动机启动
电动机的控制在改造之前是Y一△启动方式,
启动时的冲击电流比较大,且有二次电流冲击,威胁
厂用电供电安全。该启动方式最主要的缺点是直接
停泵。由于是瞬问停泵,水泵的扬程高、流量大,停
泵时止回阀、底阀也瞬时关闭使管道内产生的“水
锤”效应很大,造成对止回阀、底阀、水泵的反惯性
冲击,导致底阀破裂漏水;同时剧烈的振动也