[提要] 某厂房混凝土结构检查发现部分框架柱和梁出现了不同程度的混凝土开裂和钢筋锈蚀,鉴定为盐酸
腐蚀事故。混凝土结构受盐酸腐蚀既有酸化腐蚀的特点,又有氯化物腐蚀的特征。基于鉴定结果,建议尽快
加固或拆除该厂房。结构设计时应根据工程的环境条件,按相关规范的有关规定采取必要的结构措施和防腐
措施,以免影响结构的安全耐久性。
[关键调] 混凝土结构 酸化腐蚀 氯化物腐蚀 事故
鉴定
Appraisal and Analysis for Hydrochloric Acid Corrosion Accident of Concrete Structure/Diao Xueyou(Zhuhai Buildin
Appraisal Institute,Zhuhai 519015,China)
Abstract:There are different degrees of damage on the concrete and steel bars of some columns and beams in a pla
appraised as a hydrochloric acid corrosion accident of concrete structure. The hydrochloric acid corrosion has characteristics of
acid comosion and chloride corrosion. Based on the test results,it is suggested that the plant should be strengthened or
demolished as soon as possible,and the structural and antiseptic measures should be adopted according to the environment
condition and the relative codes for the safety and durability of the structure.
Keywords:concrete structure ;acid corrosion ; chloride cornosion ; accident; appraisal
1
工程概况
③一个边角的纵向受力钢筋和钢箍几乎已整段锈蚀,
某厂房为3层3跨现浇钢筋混凝土框架结构,平
见图 2,其他典型的损伤见图 3 - 7。
面尺寸16mx24m(图1),高9.3m,采用C25混凝土,未
采取防腐蚀措施。工程于1995年底竣工,1999年1月
起生产食品香料,主要产品为甲基环戊烯醇酮(俗称
MCP),其主要原料有:甲醇、甲醛、二甲基呋喃、食品级
盐酸和烧碱。可见,该厂混凝土结构处于有氯化物存
在的工业环境之中。2004年7月该厂所在地域安监局
在安全生产大检查中发现其框架柱、梁出现较大裂缝,
故委托珠海市房屋安全鉴定所对其进行鉴定。
图2层1柱0-③的腐蚀情况
图3层1柱0-0钢筋腐蚀状况
2.2 检测
为评估该厂房混凝土结构累积损伤的原因及其危
害,采用钻芯法检测了 11 根柱和 2 根梁的混凝土抗压
5000
1
24000
强度,检测了首层柱®-3,C-③纵向受力钢筋、钢箍
②(
和层2轴①中间跨框架梁底部纵向受力钢筋的力学性
图1±0.00柱网平面布置
能,还从现场抽取了若干混凝土试件进行化学试验。
腐蚀事故检测鉴定与分析
有关的检测结果见表1-3。
2.1 现场检查
3 腐蚀机理分析及结构安全性评估
现场检查发现,厂房的部分框架柱和梁出现了不
已研究的盐酸对混凝土的腐蚀机理表明,受盐酸
同程度的裂损,裂缝宽度大多超过1mm;轻轻敲击,保
腐蚀后的混凝土强度会降低,其强度损失率与腐蚀时
护层就会大面积剥落;裂损部位的主要受力钢筋和钢
间、盐酸溶液浓度成正比[8]。表1显示,该厂房抽检柱
箍有明显锈斑,该处混凝土呈紫褐色。其中层1柱@-
和梁的混凝土强度换算值大多为设计强度C25的60%