青海高寒地 区某双曲线 冷却塔通风筒混凝土渗水 、冻融破坏严重,通过调查该项 目设计资料 、现 场勘察 、冷却塔通风筒混凝土钻芯取样等工作 ,并在实验室进行混凝土抗 压强度 、抗冻性和抗 渗性能试验 ,对冷 却塔通风筒混凝土耐久性损伤进行分析并提 出处理措施 。 关键词 :高寒地区 ;冷却塔通风筒 ;混凝土 中 图分 类 号 :TU755.7 文献 标 识码 :B 文 章 编号 :1000—4726(2013)06—0559—03 ANALYSIS 0F DETECTION AND ASSESSM ENT FoR HYPERBoLIC CooLING TOW ER VENTILAToRS IN ALPINE REGIoN oF QINGHAI YANG Li-feng (CivilEngineeringSchoolofQinghaiUniversity,810016,Xining,China) Abstract:The seepage,freezing and thawing damage ofa hyperbolic cooling towerventilation tube concrete in the alpine region ofQinghai,based on the projectdesign,the site investigation,the concrete drillcore sampling work ofthe hyperbolic cooling towerventilators ,and according to the corresponding testofcompressive strength,frost resistance and impermeability for the cooling tower ventilators concrete,to do evaluation and analysisforthe concrete durability ofthe cooling towerventilators,According to appraisal an alysisresultsofthe cooling tower ventilator concrete,and puts forward treatment measures and reinforcement opinion for the future similarotherappraisal work and related research to provide practicalengineering experience. Key words:alpine region;cooling towerventilators;concrete 青海高寒地区某双曲线冷却塔始建于2005年 ,筒 壁 始建 于2007年 ,该 冷却塔 于2009年 开始使 用至 今 已4 年时间 ,其所处环境干旱 ,空气中含有盐分 ,日温差大, 冬天寒冷 。该塔主体结构为混凝土结构双曲线冷却塔 , 塔 筒和斜支柱 为C30混凝土,抗冻 等级为F300,抗渗等 级为P8。通风简为现浇混凝土双曲线薄壳结构 ,筒壁 最厚为400ITlm,最薄处130mm,塔筒高55.009ITI。 由于该双曲线冷却塔的通风筒为高耸薄壳结构 , 和斜支柱均处于高温高湿冻融交替及 日晒雨淋的工作 环境中.并且冷却水 中还含有对混凝土有侵蚀性的成 分 。因此冷却塔的施工质量会直接影响其寿命。 1 冷却塔 的通风筒检测 区域 的确定 1.1 通 风 简竖 向层位 划分 根 据 《工业建筑可 靠性鉴 定标 准》(GB50144- 2008),将冷却塔 的通风筒自下而上按施工段分成44层 (图 1)。